Guide
Pallet storage: regulations and fire safety at a glance
Three sets of rules mainly apply to pallet warehouses: building law with the industrial building guideline (fire compartments, storage height, extinguishing systems), occupational safety law with the Ordinance on Industrial Safety and Health and DGUV rules (racking inspection, load notices), and the workplace rules (traffic routes, fire extinguishers). The operator of the warehouse is responsible; as the depositor you provide the details of the goods.
Anyone storing pallets, or having them stored, soon runs into questions about regulations: how high may goods be stacked, how often must racking be inspected, when are sprinklers required? This guide summarises the main rules from primary sources – building code, model industrial building guideline, Ordinance on Industrial Safety and Health, DGUV information and technical rules for workplaces. It does not replace a fire safety concept or expert advice; it shows what to look out for and what to ask a provider.
At a glance
| Set of rules | Issued by | What it covers for pallet warehouses |
|---|---|---|
| State building code (in Brandenburg the BbgBO) | federal state | basic fire safety duty, building permit |
| Industrial building guideline | model of the Conference of Building Ministers, adopted by the states | fire compartments, storage sections, storage height, extinguishing systems |
| Ordinance on Industrial Safety and Health (Section 14) | federal government | inspection of work equipment such as racking |
| DGUV Information 208-043, EN 15635 | accident insurance, standardisation | racking inspection, load notices, damage |
| ASR A1.8, ASR A2.2 | Committee for Workplaces | width of traffic routes, fire extinguishers, fire wardens |
Building code: the basic fire safety duty
The starting point is the state building code. Section 14 of the Brandenburg Building Code requires structures to be arranged, built, altered and maintained so that the outbreak of fire and the spread of fire and smoke are prevented and, in the event of fire, people and animals can be rescued, rooms can be cleared of smoke and effective firefighting is possible. The Berlin Building Code contains an equivalent basic duty.
How this duty is met in a specific case is set by the building permit and the warehouse's fire safety concept. For storage and production buildings, the industrial building guideline specifies the requirements.
Industrial building guideline: storage height, storage sections, sprinklers
The model industrial building guideline of the Conference of Building Ministers (version May 2019) applies to industrial and commercial buildings used for production or storage. For warehouses it contains two particularly well-known rules; they apply to verification under Section 6 of the guideline, and other verification methods are possible. The states adopt the guideline through their administrative regulations on technical building rules; what counts are the adopted version and the approved fire safety verification.
| Rule (MIndBauRL) | Content |
|---|---|
| No. 6.4.1 – without automatic extinguishing system | divide each fire compartment or storage area into storage sections of no more than 1,200 m² by clear spaces |
| Width of clear spaces | at least 3.5 m for storage heights up to 4.5 m, at least 5.0 m at 7.5 m; interpolate in between |
| No. 6.4.2 | automatic extinguishing systems for storage heights (top edge of goods) above 7.5 m |
| No. 2 – scope | further requirements possible, e.g. for racking with combustible goods above 9.0 m top-edge storage height |
Racking: inspection and load notices
Racking is work equipment. Under Section 14 of the Ordinance on Industrial Safety and Health, work equipment exposed to damaging influences must be inspected periodically by a person competent to inspect it. DGUV Information 208-043 explains that this is to be expected above all for racking loaded and unloaded by forklifts or other industrial trucks. EN 15635 specifies the so-called expert inspection at intervals not exceeding twelve months; in addition there are internal inspections at shorter intervals, for example weekly or based on a risk analysis.
Load notices must be displayed on the racking: under EN 15512 at least the maximum permitted weight of the load unit and the maximum permitted bay load. The DGUV information also points out that the bending stress in the beam doubles if a point load sits in the middle of the shelf instead of an evenly distributed load – then only half the shelf load is permitted. For your goods this means that pallet weight and load distribution are no side issue.
Traffic routes and fire extinguishers under the workplace rules
Technical rule ASR A1.8 sets the minimum width of routes for vehicle traffic: for single-lane vehicle traffic below 20 km/h, the largest width of vehicle or load plus twice 0.50 m margin allowance. For two-way traffic the width of the second vehicle or its load and a 0.40 m passing allowance are added; with shared pedestrian and vehicle traffic the margin allowance is 0.75 m on each side.
ASR A2.2 covers fire extinguishers and fire wardens: it sets a maximum actual walking distance of 20 m to the nearest extinguisher, a grip height of 0.80 m to 1.20 m is considered practical, and a share of 5 % of employees as fire wardens is usually sufficient.
What this means for you as the depositor
Most duties lie with the warehouse operator. Your part is complete information about the goods: weight and dimensions of the pallets, whether they are stackable, packaging material and special properties. If dangerous goods are to be stored, Section 468(1) HGB requires a commercial depositor to notify the warehouse keeper in good time and in text form of the exact nature of the danger and any precautions to be taken – details in the guide warehousing contracts under the HGB. We do not accept dangerous goods for storage.
How pallet height and weight also determine the price is shown in pallet space costs; how storage works with us is described in pallet storage.
- Is there evidence of the last racking inspection?
- Which load notices apply to the intended rack bays?
- Are there requirements on height, weight or packaging of your goods?
- How are the goods insured, and what does the insurer require?
Typical mistakes
- Pallet weight estimated instead of weighed, causing the permitted load to be exceeded
- Heavy load placed in the middle of the shelf instead of spread across the beams
- Goods stacked above the agreed height
- Racking damage after an impact not reported
- Combustible packaging (e.g. a lot of film or foam) not declared
Key terms
- Storage height: height of the top edge of the stored goods, decisive for many fire safety requirements
- Storage section: part of a storage area separated by clear spaces
- Automatic extinguishing system: system that activates without human intervention, e.g. sprinklers
- Bay load: permitted total load of a racking bay between two frames
- Competent person: person with expertise to inspect work equipment under the Ordinance on Industrial Safety and Health
An overview, not fire safety advice
This guide gives an overview of general rules and is not legal or fire safety advice. What counts is the version of the guidelines adopted in the respective state, the building permit and the warehouse's fire safety concept.
Questions and answers: Pallet storage regulations
How often must pallet racking be inspected?
Racking loaded by forklift must be inspected periodically by a competent person. EN 15635 specifies at least once every twelve months for the expert inspection, plus shorter internal inspections.
When are automatic extinguishing systems required?
Under No. 6.4.2 of the model industrial building guideline, automatic extinguishing systems are required for storage heights above 7.5 m (top edge of goods). What counts is the version adopted in the state.
How wide must aisles in a pallet warehouse be?
Under ASR A1.8, for single-lane vehicle traffic below 20 km/h, at least the largest width of vehicle or load plus twice 0.50 m; for two-way traffic add the second vehicle and 0.40 m, with mixed traffic 0.75 m on each side.
How high may pallets be stacked?
There is no fixed figure. What matters are the racking load notices, the stackability of goods and pallet, and the building's fire safety, which is based on the storage height.
Who is responsible for fire safety in the warehouse?
The operator of the warehouse. As the depositor you must provide complete details of the goods, in particular any dangerous properties.
Sources
- Brandenburgische Bauordnung (BbgBO), § 14 Brandschutz (accessed 2026-11-11)
- Muster-Industriebau-Richtlinie (MIndBauRL), Stand Mai 2019 – Veröffentlichung Land Hessen (accessed 2026-11-11)
- DGUV Information 208-043 „Sicherheit von Regalen“ (Juni 2020) (accessed 2026-11-11)
- § 14 Betriebssicherheitsverordnung – Prüfung von Arbeitsmitteln (accessed 2026-11-11)
- BAuA: ASR A1.8 Verkehrswege (accessed 2026-11-11)
- BAuA: ASR A2.2 Maßnahmen gegen Brände (accessed 2026-11-11)